Credit: ABB
See above picture, have you seen this type of thing in your home ??? This is MCB .. in the above picture, four nos MCB are shown.
MCB means Miniature Circuit Breaker .. Miniature dictionary means small form of some big item ..
So what a MCB does? Why u need MCB?
See the below picture where electricity reaches to lights through a MCB.
Overload
Under normal conditions, lights take only 10 amp but due to some problems, lights take 15 amp more than rated current.
This is overload of lighting circuit and MCB disconnects (or trips ) the lighting circuit, thus saving failure. lights
Now consider below picture in which wire between light and MCB becomes short or ground or develop a shot circuit than a heavy current will flow through the MCB and MCB trips immediately ..thus MCB saves wiring or circuit to complete distrcution or develop a fire.
Shot Circuit
So a MCB provide protection against overload and short circuit. So because of this , it is being used.
Construction of MCB:
See below picture in which cross section (inside view) of MCB is shown.
Types of MCB:
Based on the poles
- Single Pole MCB (SP)
- Single Pole + Neural MCB(SPN)
- Double Pole MCB(DP)
- Tripple/Three Pole MCB(TP)
- Three Pole MCB +Neutral (TPN)
- Four Pole MCB(FP)
Difference between Three pole +Neutral MCB and Four Pole MCB : both types of MCB looks similar but in four pole MCB, protection is provided for three phases and neutral while in case of three pole + Neutral(TPN), protection is provided only in three phases, not for neutral.
Types of MCB based on Tripping Curves
Based on tripping curves or tripping characteristics, MCB are divided into following types.
- B Curve MCB
- C Curve MCB
- D Curve MCB
- K Curve MCB
- Z Curve MCB
Confused?? What is tripping curve and what is difference in between B, C & D and Z, K type curves MCBs.
B Type MCB:
See below picture .
So what you see above ..its a graph ..between circuit current (In) and time(t) in seconds ..
at various values of circuit current i.e. 0.5, 1, 2, 3, 5,7 ,10 times of the circuit current, MCB behaviour is checked and time taken by MCB to trip is noted .
and a graph is drawn between current flowing through circuit or MCB and tripping time of MCB. This is known as tripping curves or tripping characteristics of MCB.
Now look at the tripping curves once again
And look how much MCB takes time to trip when 2 times of circuit current is flowing ..whats the time from graph ..its 15 seconds ..Right ?
Now check what is MCB Tripping time when 3 times current is flowing ?
Now what you see on graph ? Time is 0.03 seconds
Why so much difference ..
- MCB tripping time at 2 times current = 15 seconds
- MCB tripping time at 3 times current= 0.03 seconds
Because B type MCB see 2 times current as thermal overload and see 3 times current as short circuit.
C Type MCB:
Now see the curves of C type MCB
It looks similar to B type MCB curve at one instance ..but look close and compare both the curves
What you have seen ?
B type MCB trips on 3 times rated current in 0.03 seconds while C type MCB takes 2 seconds to trip on 3 times of current.
C type MCB trips in 0.03 seconds on 5 times of circuit current.
So this is difference ..C type MCB consider short-circuit from 5 times of circuit current while B type consider short circuit from 3 times of current.
D type MCB:
In D type MCB, short circuit is given from 10 times of rated current.
So what you learn
- B Type MCB see short Circuit or gives instant tripping from 3 times of rated current
- C type gives instant tripping on and over 5 times of rated current.
- D type gives instant tripping on and over 10 times of rated current
But in pratice, it is not so B type MCB designed and available in the market with instant tripping @ 3-5 times of rated current.
Means some B type MCB instant tripping can start from 3 or for some MCB, from 4 or for some MCB, its from 5 so each B type MCB tripping curve is not same.
Similarly, C type MCB have tripping range between 5-10 times rated current.
And D type have range of 10-20 times rated current.
Tripping curves showing instant or short circuit tripping range of B, C and D type MCBs, shown below.
As can be seen from the above picture, B type MCB instant tripping may be start from 3 to 5 times of rated current.
As can be seen from the above picture, C type MCB instant tripping may be start from 5 to 10 times of rated current.
As can be seen from the above picture, D type MCB instant tripping may be start from 10 to 20 times of rated current .
K Type MCB
K type MCB has instant tripping range from 10 to 14 times of rated current.
Z Type MCB
Z type MCB has instant tripping range from 2 to 3 times of rated current.
In the below figure, tripping characteristics of all types of MCBs are superimposed.